Use temperature: -60℃ ~ + 100℃.
Can be used statically at high temperatures of 350℃ ~ 3000℃.
Environmental protection standard: ROHS.
Standard color: white.
Flexible structure, can adapt to the wrapping of cables and cable intermediate joints under various conditions, and easy to install.
When the cable intermediate joint or cable itself covered with ceramic composite fire blanket breaks down, it is not easy to cause a fire.
The cable intermediate joint or cable covered with ceramic composite fire blanket has the ability to resist fire. When the surrounding fire occurs, it can defend itself and ensure that the cable system has a long-term power supply capacity in the fire.
When the cable intermediate joint or cable covered with ceramic composite fire blanket is in normal operation, the heat dissipation capacity of the cable will not be affected by the covering.
Project |
|
Standard test |
Flame retardancy |
Double torches for flame supply, flame temperature greater than 750℃, AC voltage applied between conductor and metal shield - Fire supply (90min, 8.7KV) - After stopping fire supply (15min, 8.7KV) The sample does not break down when voltage is applied during the entire test duration |
TICW -8 |
Sample integrity |
Within 1 hour after the test, apply a test voltage of 3.5U0 (AC30.5kV to the cable) to the sample for 15 minutes, and there should be no breakdown |
TICW-8 |
Appearance inspection |
Cable outer sheath slightly burned or no burned |
Visual inspection |
Temperature monitoring |
750℃ fire for 1 hour, cable surface temperature ≤130℃ |
"Temperature detection test guide" |
Combustion performance |
B1 grade |
GB 8624-2012 |
Project |
Index |
Test Standard |
Density (g/cm3) (25℃) |
1.55±0.05 |
GB/T 533 |
Tensile Strength (Mpa) |
≥3.5 |
GB/T 528 |
Tear Strength (kN/m) |
≥20 |
GB/T 529 |
Breakdown strength (kV/mm) |
≥20 |
GB/T 1695 |
Volume resistivity (Ω.cm) |
≥1* 1013 |
GB/T 1692 |
Smoke toxicity |
ZA1 |
GB/T 20285 |
Model |
Thickness (mm) |
Length (mm) |
Width (mm) |
Area (m2) |
SMLCFB-01 |
15-20 |
600 |
800 |
0.48 |
SMLCFB-02 |
15-20 |
800 |
800 |
0.64 |
SMLCFB-03 |
15-20 |
1000 |
800 |
0.8 |
SMLCFB-04 |
15-20 |
1200 |
1000 |
1.2 |
SMLCFB-05 |
15-20 |
1500 |
1000 |
1.5 |
Applicable to fire protection of medium and low voltage power cable connections of various specifications.
Chemical, building materials, places around smelting blast furnaces that require fire protection, cables and cable accessories, and cable trench fire protection projects.